Connection command:

First, close the entrance door, so that it locks completely, then put the handle in place of the earthing shaft, turn it counterclockwise to remove the sectioner from the earthing mode (after earthing, a mechanical interlock is established, which does not open the door in any way) can’t). After earthing, remove the handle from the earthing shaft. Turn the switch on the sectioner counterclockwise to open the connecting and disconnecting shaft input valve. Place the handle in the disconnecting and connecting shaft by turning the sectioner shaft clockwise. It connects then remove the handle. (Hand pressure should be enough to remove the handle easily). After connecting the sectioner, move the switch to the degenerator probe. Turn the switch counterclockwise. After charging the spring, you can connect the degenerator by pressing the green button (ON).

Interrupt command:

To cut off the degenerator, press the red (OFF) button, the degenerator will be cut off. While keeping your thumb (OFF), turn the switch 180 degrees clockwise and remove the degenerator from the switch and insert it into the sectioner and turn it counter-clockwise. The shaft inlet valve is opened by placing the handle in The shaft of the sectioner is cut off by turning it counter-clockwise. After disconnecting the sectioner, put the handle in the place of the earth shaft and turn it clockwise until it is earthed, now you can open the door.